A worked example
A 24 V device drawing 1 A at the end of a 400 foot run, with 10% of the supply voltage available to lose, needs 14 AWG. That drops 2.02 V, or 8.4% of the supply, leaving 21.98 V at the device.
One size smaller, 16 AWG, drops 3.21 V — 13.4% — which is over the allowance. That is the whole calculation: step up through the sizes until one holds, and stop there rather than going two sizes larger out of caution and paying for copper you do not need.
How the size is chosen
The allowable drop sets a maximum resistance for the circuit, and each gauge has a resistance that follows from its diameter. Rearranged:
allowed drop = volts x percent / 100
max resistance = allowed drop x 1000 / (2 x length x current)The 2 is there because the current goes out on one conductor and returns on the other, so the circuit contains twice the run length in wire. The sizes are then tried from smallest upwards, and the first one whose resistance per 1000 feet falls under that maximum is the answer. Resistance itself is derived from the gauge, not looked up; the voltage drop calculator sets out the formula and the check against published figures.
If no size on the list is large enough, this says so rather than returning the biggest one. A run that cannot be done in 2 AWG needs a different design — a supply nearer the load, a higher distribution voltage, or a device that tolerates less voltage — not a thicker cable.
What this does not tell you
- It sizes for voltage drop only. Ampacity is a separate limit set by the wiring method and the installation, and a conductor that passes here can still be too small to carry the current safely.
- It will not tell you what drop is acceptable. That comes from the minimum operating voltage on the device's data sheet. Leave margin for a battery supply, which sags under load, and for a long run that will be warmer than the bench.
- It assumes copper, direct current, and a single load at the far end.
- It does not know what will fit in the conduit. For that, see the conduit fill calculator.
Other tools
- Voltage dropHow much voltage a run loses, and how much reaches the device at the end of it.
- PoE budgetWhat a set of cameras and door controllers asks of the switch feeding them.
- CCTV storageHow much disk a retention period needs, and how long an array will last.
- CCTV bandwidthWhat the cameras ask of the switch, recording and while being watched.
- RAID capacityWhat an array really gives you, and how many disks can fail.
- Conduit fillWhether the cable you are pulling fits the conduit, and how much room is left.
- Resistor colorsWhat the bands mean, and which resistor a supervised zone wants.
- Ohm's lawAny two of volts, amps, ohms and watts give the other two.
- Speaker loadWhether the amplifier covers the taps, with reserve left over.
- IP subnetWhat a prefix really holds, and how to carve one up by system.
- Address planThe commissioning address list, before you are up a ladder.