Conduit fill calculator

Pick the conduit or type its diameter in, then the cables going in it. Cable outside diameters come off your own data sheets, because those genuinely vary by maker.

Conduit

Filled from the trade size above. Type over it for flexible conduit, innerduct, surface raceway or anything measured on site — nothing below depends on the picker.

Cables

A worked example

Cables of 0.25 inch outside diameter into 1 inch EMT, whose bore is 1.049 inches. Each cable occupies 0.0491 square inches and the conduit has 0.8643 square inches inside it, of which 40% — 0.3457 square inches — may be filled when there are more than two conductors.

That makes 7 the most that will go in: 7 cables take 0.3436 square inches, or 39.8% of the conduit, which is inside the limit. Cable number 8 would take it to 45.4% and over.

How fill is worked out

Each cable is treated as a circle and the areas are added up, then compared against the conduit's internal area:

cable area   = pi x (OD / 2) ^ 2
used         = sum of (count x cable area)
conduit area = pi x (internal diameter / 2) ^ 2
fill         = used / conduit area

The permitted fill depends on how many conductors there are, which is the part worth getting right: one conductor is allowed the most room and two the least.

Maximum conduit fill by number of conductors
ConductorsMaximum fillSection
1 conductor53%NEC Chapter 9, Table 1
2 conductors31%NEC Chapter 9, Table 1
More than 2 conductors40%NEC Chapter 9, Table 1
Nipple, 24 in or less60%NEC Chapter 9, Table 1, Note 4

Trade size is not a diameter

A trade size is a label, not a measurement: half-inch conduit has no dimension that is half an inch. The bore is 0.622 in for EMT, 0.659 in for IMC, and 0.632 in for RMC. That is why the picker above asks for a type as well as a size — keyed on size alone it would be wrong for two of the three.

The internal diameters below are not copied from a table. Each one is worked out from the outside diameter and wall thickness the Steel Tube Institute publishes for that size, with the wall crossed twice because it sits on both sides of the bore:

inside diameter = outside diameter - 2 x wall thickness

1 in EMT: 1.163 - 2 x 0.057 = 1.049 in

Which type gives the most room is not a fixed ranking, and it is worth checking before substituting one for another. IMC has the widest bore up to 2 in; from 2 1/2 in up it is EMT. IMC leads at the small sizes because its wall is thinner than rigid's while its outside diameter is larger than EMT's, and loses the lead further up because EMT's wall stays thin while the others thicken.

Why it asks you for the cable diameters

Two reasons. The first is that it gives the right answer: a shielded 22/4, a plenum Cat6 and a riser-rated composite cable of nominally the same build differ in outside diameter between manufacturers, and the published wiring tables do not list most low-voltage cable at all. The number on your data sheet is the number in your conduit.

The second is that the fill percentages above are facts that can be cited by section, while the dimension tables are another matter. Those tables are part of a copyrighted document. Formulas and facts are not copyrightable, so deriving from a diameter you supply is both safer and more accurate than reproducing somebody else's table.

The limits here are NEC Chapter 9, Table 1, with the nipple allowance at NEC Chapter 9, Table 1, Note 4. The edition in force where your property sits is the one that applies, and local amendments are common — check with the authority having jurisdiction before a submittal.

Steel conduit dimensions

Nominal figures, as published. Measure anything that matters, and anything that has been in the ground.

EMT — electrical metallic tubing
SizeODWallInside
1/20.7060.0420.622
3/40.9220.0490.824
11.1630.0571.049
1 1/41.5100.0651.380
1 1/21.7400.0651.610
22.1970.0652.067
2 1/22.8750.0722.731
33.5000.0723.356
3 1/24.0000.0833.834
44.5000.0834.334
IMC — intermediate metal conduit
SizeODWallInside
1/20.8150.0780.659
3/41.0290.0830.863
11.2900.0931.104
1 1/41.6380.0951.448
1 1/21.8830.1001.683
22.3600.1052.150
2 1/22.8570.1502.557
33.4760.1503.176
3 1/23.9710.1503.671
44.4660.1504.166
RMC — rigid metal conduit
SizeODWallInside
1/20.8400.1040.632
3/41.0500.1070.836
11.3150.1261.063
1 1/41.6600.1331.394
1 1/21.9000.1381.624
22.3750.1462.083
2 1/22.8750.1932.489
33.5000.2053.090
3 1/24.0000.2153.570
44.5000.2254.050
55.5630.2455.073
66.6250.2666.093

What this does not tell you

  • It is a cross-sectional area check only. It says nothing about whether the pull is physically achievable: bends, total pull length, lubrication and jacket friction all decide that, and a conduit at 39% fill around four 90-degree bends is a bad afternoon.
  • It does not consider derating, bundling or heat. Power conductors bundled in a conduit carry less current than the same conductors in free air.
  • It treats every cable as a circle. Flat and oval cable, and cable that flattens under tension, do not behave that way.
  • It does not know whether these cables may share a conduit at all. Mixing power and signaling circuits is governed by the wiring method and the circuit types involved, not by how much room is left.