Ohm's law calculator

Fill in any two of voltage, current, resistance and power, and the other two follow. The working is shown, because the working is the useful part.

Enter exactly two. Clear a box to change which two you are working from.

A worked example

A 12 V siren drawing 0.5 A. Resistance is voltage divided by current, so 12 ÷ 0.5 = 24 Ω. Power is voltage times current, so 12 × 0.5 = 6 W.

The power figure is the one that matters on a job. Six watts sounds small until there are eight of them on one supply, and a power supply sized on the number of devices rather than the sum of their draw is the usual reason a panel browns out when everything sounds at once.

Any two give you the other two

Four quantities, six pairs. The formula used depends on which two you have, which is the whole content of the thing:

Which formula applies to each pair of known quantities
If you knowYou getBy
V and I (voltage, current)R and PR = V ÷ I P = V × I
V and R (voltage, resistance)I and PI = V ÷ R P = V² ÷ R
V and P (voltage, power)I and RI = P ÷ V R = V² ÷ P
I and R (current, resistance)V and PV = I × R P = I² × R
I and P (current, power)V and RV = P ÷ I R = P ÷ I²
R and P (resistance, power)V and IV = √(P × R) I = √(P ÷ R)

What the letters are

  • V — voltage, measured in volts.
  • I — current, measured in amps.
  • R — resistance, measured in ohms.
  • P — power, measured in watts.

Current is the one people reason about least and that decides the most: it sets the conductor you need, the voltage you lose along it and the heat in the bundle.

Where it stops being this simple

  • This is direct current. Alarm, access control and camera circuits mostly are, so it applies. Anything with a motor, a transformer or a long run of alternating current has reactance as well as resistance, and you need impedance instead. This will read low on those.
  • Resistance moves with temperature. Copper is about 0.4% more resistive per °C, so a conductor in a hot plenum is not the conductor on the bench. The voltage drop calculator takes a conductor temperature for that reason.
  • Devices are not resistors. A siren, a camera or a card reader draws what its electronics ask for, which changes between idle and alarm and is not a fixed resistance. Use the figures on the data sheet, and the alarm-condition figure rather than the standby one when sizing a supply.
  • It says nothing about whether a conductor can carry the current safely. That is ampacity, set by the wiring method and the installation.

The other half of the question

Knowing the current is the start. What it costs you over a long run is voltage drop, and the conductor that keeps it inside an allowance is wire size. For a loop with a supervision resistor in it, the resistor color code tells you what the band colors mean.

Sizing a system rather than a circuit?

Power supplies, battery backup and conductor sizing are part of the design when we install a system, not something worked out on site afterwards.

Other tools

Free consultation

Tell us about the property and what it needs.

We will look at the building, the risks and the way it is used, then quote a system that fits. No charge for the conversation.

Call nowRequest a quote