Voltage drop calculator

Enter the gauge, the length of the run and the current the device draws. The resistance is derived from the gauge, not read off a table.

A worked example

A 12 V siren drawing 0.75 A at the end of a 250 foot run of 18 AWG is the case that catches people out. The current travels out along one conductor and back along the other, so the resistance that matters is that of 500 feet of wire, not 250.

18 AWG is 6.3849 ohms per 1000 feet at 20 °C. That gives a drop of 2.39 V, which is 20.0% of the supply, leaving 9.61 V at the siren. Most 12 V devices stop behaving predictably well before that, which is why the run either needs a larger conductor or a supply closer to the load.

How the figure is worked out

There is no wire table behind this. AWG is a geometric series, so the conductor diameter follows from the gauge number, and the resistance follows from the diameter:

diameter (in) = 0.005 x 92 ^ ((36 - n) / 39)
area          = pi x (diameter / 2) ^ 2
resistance    = rho / area, with rho = 1.7241e-8 ohm-meters
drop          = 2 x length x current x resistance per 1000 ft / 1000

The resistivity is the IACS value for 100% annealed copper at 20 °C. Warmer copper is more resistive, by about 0.393% per °C, which is the temperature selector above. At the 75 °C conductor rating the resistance is 1.2162 times the 20 °C figure.

Checked against published resistance figures for 10 through 22 AWG, the derived values are within 0.023%. The check runs in this site's test suite rather than being a claim made here.

Copper resistance by gauge

Ohms per 1000 feet of one conductor, computed from the formula above.

DC resistance of copper conductors in ohms per 1000 feet
SizeAt 20 °CAt 75 °C
24 AWG25.668231.2164
22 AWG16.142919.6322
20 AWG10.152412.3468
18 AWG6.38497.7650
16 AWG4.01554.8834
14 AWG2.52543.0712
12 AWG1.58821.9315
10 AWG0.99881.2147
8 AWG0.62820.7640
6 AWG0.39510.4805
4 AWG0.24850.3022
2 AWG0.15630.1900

What this does not tell you

  • It is a direct-current calculation. For alternating current over long runs, inductive reactance adds to the impedance and this will read low.
  • It says nothing about ampacity. A conductor can hold the voltage drop comfortably and still be too small to carry the current safely, which is a separate question governed by the wiring method and the installation.
  • It assumes copper. Aluminium is roughly 1.6 times as resistive for the same gauge.
  • It assumes one load at the far end. A run with devices tapped along its length drops less than this, because not all the current travels the whole way.

How much drop is acceptable is set by the device, not by this page: use the minimum operating voltage on the manufacturer's data sheet, and leave margin for a battery supply that will sag under load.