A worked example
Red, red, red, gold. The first two bands are the digits — red is 2 and red is 2, so 22. The third is the multiplier, and red there means ×100. That gives 2.2 kΩ. Gold is the tolerance band at ±5%, so the part is anywhere from 2.09 kΩ to 2.31 kΩ and still in specification.
That is the resistor most likely to be in your hand on a service call, because 2.2 kΩ is a common end-of-line supervision value.
Why an alarm technician needs this
A supervised zone puts a resistor at the far end of the loop so the panel can tell the difference between a closed contact and a cut wire: the loop reads a specific resistance when it is healthy, open when it is cut and short when it is shorted. The panel expects a particular value, and fitting the wrong one gives a zone that reads trouble, or worse, one that reads normal when it has been defeated.
So the resistors in a bag of spares matter, and they are identified by their bands. The values below are the ones that turn up.
| Value | Bands at ±5% | In specification between |
|---|---|---|
| 1 kΩ | brown, black, red, gold | 950 Ω – 1.05 kΩ |
| 1.5 kΩ | brown, green, red, gold | 1.425 kΩ – 1.575 kΩ |
| 2.2 kΩ | red, red, red, gold | 2.09 kΩ – 2.31 kΩ |
| 3.3 kΩ | orange, orange, red, gold | 3.135 kΩ – 3.465 kΩ |
| 4.7 kΩ | yellow, violet, red, gold | 4.465 kΩ – 4.935 kΩ |
| 5.6 kΩ | green, blue, red, gold | 5.32 kΩ – 5.88 kΩ |
| 6.8 kΩ | blue, grey, red, gold | 6.46 kΩ – 7.14 kΩ |
| 10 kΩ | brown, black, orange, gold | 9.5 kΩ – 10.5 kΩ |
The code itself
One scale does most of the work: the same ten colors that carry the digits 0 to 9 are the multiplier band read as a power of ten. Black is 0 and ×1, brown is 1 and ×10, red is 2 and ×100, and so on. Gold and silver carry no digit and divide instead, which is how sub-ohm parts are marked.
| Color | Digit | Multiplier | Tolerance | Temp. coeff. |
|---|---|---|---|---|
| black | 0 | ×1 | — | — |
| brown | 1 | ×10 | ±1% | 100 ppm/°C |
| red | 2 | ×100 | ±2% | 50 ppm/°C |
| orange | 3 | ×1,000 | — | 15 ppm/°C |
| yellow | 4 | ×10,000 | — | 25 ppm/°C |
| green | 5 | ×100,000 | ±0.5% | — |
| blue | 6 | ×1,000,000 | ±0.25% | 10 ppm/°C |
| violet | 7 | ×10,000,000 | ±0.1% | 5 ppm/°C |
| grey | 8 | ×100,000,000 | ±0.05% | 1 ppm/°C |
| white | 9 | ×1,000,000,000 | — | — |
| gold | — | ×0.1 | ±5% | — |
| silver | — | ×0.01 | ±10% | — |
Which band is which
- Four bands. Two digits, a multiplier, a tolerance. The ordinary kind, and what a ±5% part looks like.
- Five bands. Three digits, a multiplier, a tolerance. Three digits is how a precision part carries a value like 2.26 kΩ that two digits cannot express.
- Six bands. As five, plus one more. That last band is usually a temperature coefficient in parts per million per °C — but not always. Some manufacturers have used it for a reliability or failure-rate figure, and the published values for it are not consistent between sources. Treat a sixth band as a hint and the datasheet as the answer.
A resistor with no tolerance band at all is ±20%, which is rare on anything made recently.
Reading direction, and the part that catches people
The bands are read from the end they are grouped towards, which is usually the end away from the tolerance band. Gold and silver are the giveaway: a gold or silver band at one end is nearly always the tolerance, so that end goes on the right. On a part where the grouping is ambiguous, measure it — the colors are a label, and a meter is a measurement.
Brown, red and orange are hard to tell apart under a flashlight in a riser, and a discolored part is worse. If a zone will not settle, the resistor you believe is a 2.2 kΩ is worth a meter before it is worth an argument.
Where these figures come from
The digits, multipliers and tolerances are the standard color code, published consistently across manufacturer and distributor charts. The underlying standard is IEC 60062, which is not free to read, so nothing here is quoted from it; the figures are the ones every published chart agrees on. The sixth band is the exception noted above, where the sources do not agree with each other.
Full notes and the fixtures: docs/resistor-color-code.md in the site's repository.
Zone trouble that will not clear?
Supervision faults are usually a wiring or termination problem rather than a panel problem. We service and take over existing systems across Illinois.
Other tools
- Voltage dropHow much voltage a run loses, and how much reaches the device at the end of it.
- Wire sizeThe smallest conductor that still gets the device enough voltage.
- PoE budgetWhat a set of cameras and door controllers asks of the switch feeding them.
- CCTV storageHow much disk a retention period needs, and how long an array will last.
- CCTV bandwidthWhat the cameras ask of the switch, recording and while being watched.
- RAID capacityWhat an array really gives you, and how many disks can fail.
- Conduit fillWhether the cable you are pulling fits the conduit, and how much room is left.
- Ohm's lawAny two of volts, amps, ohms and watts give the other two.
- Speaker loadWhether the amplifier covers the taps, with reserve left over.
- IP subnetWhat a prefix really holds, and how to carve one up by system.
- Address planThe commissioning address list, before you are up a ladder.